Navien Water Heater Not Getting Hot Enough

On this page (8 sections)

The Short Answer: If a Navien fires but the water never gets as hot as the setting, check the setting and measure the water at the tap nearest the heater. Navien’s troubleshooting chart lists two causes: the setting is too low, or hot and cold lines are cross-plumbed. Beyond those, look at winter demand beyond the heater’s capacity, scale, a clogged inlet filter, or low gas supply.

Measure before you change anything

Use a kitchen or meat thermometer in a glass of water from the hot tap closest to the heater, with that tap fully open for a minute.

Result What it suggests
Close tap is near the setting; far taps are cooler Heat loss in long pipes, or a mixing valve or crossover on that branch
Close tap is well below the setting with one fixture running Setting, scale, filter, or gas supply
Fine with one shower, lukewarm with two The heater is at its capacity for that flow and incoming water temperature
Worse in winter than summer Larger temperature rise needed; sizing or gas supply limit
Gradually worse over months, with noise or codes Scale

If the water goes cold partway through a shower and stays cold, that’s a different problem. See Navien goes cold. If it takes a long time to arrive but then is hot, see Navien hot water takes too long.

Setting and mixing valves

The NPE-2 manual gives a normal adjustable range of 97°F to 140°F, with higher temperatures only in a commercial mode the installer enables. Check the set temperature on the front panel or app. Someone may have lowered it, or a settings reset may have changed it.

Many installations have a thermostatic mixing valve near the heater or at the shower. If it’s set low, or failing, taps stay lukewarm even though the heater is working. A shower valve’s anti-scald limit stop can also cap the temperature at that fixture only.

Crossover between hot and cold

A failed single-handle faucet or shower cartridge, or a recirculation check valve that doesn’t close, can let cold water into the hot line. Navien’s chart lists checking for cross plumbing. A sign is a cold tap running warm, or the hot water getting hotter when one particular fixture’s shutoff valves are closed.

Capacity and temperature rise

A tankless heater has a maximum heat output, so the hotter you need the water and the more water you draw, the more output it needs. A rough rule is that heating water takes about 500 Btu per hour for each gallon per minute and each degree Fahrenheit of rise. Two showers at 2 gallons per minute each, raised from 45°F to 115°F, need roughly 140,000 Btu per hour delivered to the water. Smaller models, or cold winter inlet water, can fall short. When that happens, the heater may also reduce flow to hold temperature, which feels like low pressure. See Navien low pressure.

Scale, filters and gas supply

  • Scale on the heat exchanger reduces heat transfer and eventually triggers overheating codes such as E016 or E030. Navien’s manual describes flushing the heat exchanger; see how to flush a tankless water heater.
  • A clogged inlet water filter disrupts flow and is one of Navien’s listed owner checks for E016 and E030.
  • Gas supply. A gas line too small for the heater, or a propane regulator that can’t keep up, limits how hard the burner can fire. Lukewarm water when the furnace or range is also running is a clue.

What you can check safely

  1. Check the set temperature and measure the water at the nearest tap.
  2. Try one fixture at a time.
  3. Look for a mixing valve near the heater and note its setting.
  4. Clean the inlet water filter if you’re comfortable following the owner’s manual steps.
  5. Note whether it’s worse in winter, with other gas appliances running, or over time.

What the technician will check

A technician will compare inlet and outlet temperatures and flow at the heater. They measure gas pressure with the heater at full fire and other appliances running, and check for scale and flush if needed. They also test mixing valves and look for crossovers. If the heater is undersized for your demand, they can discuss options such as adding a second unit.

Frequently Asked Questions

Q: Should I set the Navien to 140°F to get hotter showers? A: Only if a mixing valve is fitted to bring the delivered temperature back down to a safe level. Otherwise, raising the setting increases the scald risk, and it doesn’t fix a crossover or a heater that is short on capacity. Find the cause first.

Q: Can scale make it lukewarm without a code? A: Yes. Scale usually reduces performance gradually before overheating codes appear. If you have hard water and the heater hasn’t been flushed in a year or more, it’s a likely factor.

Before you call a technician

Write down

  • The heater. Photograph the rating plate: brand, full model number, serial number, and fuel. The serial number usually encodes the manufacture date.
  • The pattern. Is every fixture affected? Is the water cold, briefly hot, or lukewarm? Did it start after an outage, a freeze, plumbing work, or a setting change?

Stop and get help if

  • Gas or rotten-egg smell, or a CO alarm: leave now and call the gas utility or 911 from outside. Do not use switches or try to find the source.
  • A burner bang, flames outside the burner area, soot, or a smell of exhaust: turn the heater off at its control and do not relight it.
  • Never cap the relief valve, bypass a safety switch, or open gas, electrical, or sealed combustion parts.